A superior wraparound insulation product that easily installas in repair and splice applications providing excellent insulation and protection for cable jackets.
Features.-
-
3:1 shrink ratio
-
High shrink ratio covers even irregular shapes
-
Better split resistance than competitive products
-
Thermoplastic adhesive liner provides complete environmental protection and insulation
-
Continuous operating temperature: -45 oC to 105 oC
-
Shrink temperature: Start at 100 oC, full recovery at 130 oC
Dimensions
|
Part No. |
Inner Diameter |
Recovered wall thickness Nom. (mm) |
Standard length (mm) |
As supplied Min. (mm) |
After recovery Max. (mm) |
WRSXP-30/12 |
30 |
13 |
1.8 ± 0,2 |
500 - 1000 |
WRSXP-40/18 |
40 |
18 |
2.5 ± 0,2 |
500 - 1000 |
WRSXP-50/18 |
50 |
18 |
2.5 ± 0,2 |
500 - 1000 |
WRSXP-60/22 |
60 |
22 |
2.5 ± 0,2 |
500 - 1000 |
WRSXP-85/30 |
85 |
30 |
2.9 ± 0,2 |
500 - 1000 |
WRSXP-100/35 |
100 |
35 |
3.0 ± 0,2 |
500 - 1000 |
WRSXP-120/40 |
129 |
40 |
3.0 ± 0,2 |
500 - 1000 |
WRSXP-150/50 |
150 |
50 |
3.5 ± 0,2 |
500 - 1000 |
WRSXP- 160/50 |
160 |
50 |
3.5 ± 0,2 |
500 - 1000 |
Technical Data
|
Property |
Test Method |
Standard Value |
Tensile strength |
ASTM-D 638 |
≥ 13 MPa |
Elongation at break |
ASTM-D 638 |
≥ 300% |
Tensile strength after aging |
ASTM-D 2671/120 oC, 168 hrs |
≥ 11 MPa |
Elongation at break after aging |
ASTM-D 2671/120 oC, 168 hrs |
≥ 230% |
Volume resistance |
ASTM-D 2303 |
1 x 1014 Ω.cm |
Dielectric strength |
IEC 243 |
≥ 20 KV/mm |
Longitudinal shrinkage |
- |
≤ 10% |
Eccentricity |
ASTM-D 267 |
≤ 30% |
Water absorption |
ISO 62 |
≤ 0.1% |