Idiomas/Languages:  Español  English  

Heat Shrinkable Cable End Caps

Heat Shrinkable Cable End Cap has a good waterproof seal. Widely used in power cables and communication cable storage at the end of treatment. Also be used for street lamps and low voltage operation of the cable end of the deal.

Features.-

  • 3:1 shrink ratio
  • Superior resistance to weathering,
  • Resistant to common fluids and
  • Standard adhesive liner provides
  • Coated hot melt adhesive resists
  • Continuous operating temperature: -45 oC ~ 105 oC
  • Shrink temperature: 130 oC

Dimensions

Part No. D Main  diameter L Full Length (mm) Wall  thickness
As supplied (mm) After recovery (mm) As supplied (mm) After recovery (mm)
WRSFM-11/6 ≥ 11 ≤ 6 ≥ 30 0.7 ± 0.1 ≥ 1.1
WRSFM-16/8 ≥ 16 ≤ 8 ≥ 70 1.2 ± 0.1 ≥ 2.2
WRSFM-20/8 ≥ 20 ≤ 8 ≥ 70 1.2 ± 0.1 ≥ 2.2
WRSFM-25/11 ≥ 25 ≤ 11 ≥ 80 1.2 ± 0.1 ≥ 2.3
WRSFM-30/16 ≥ 30 ≤ 16 ≥ 90 1.5 ± 0.1 ≥ 2.5
WRSFM-35/17 ≥ 35 ≤ 17 ≥ 90 1.5 ± 0.1 ≥ 2.5
WRSFM-40/15 ≥ 40 ≤ 15 ≥ 90 1.5 ± 0.1 ≥ 2.5
WRSFM-50/26 ≥ 50 ≤ 26 ≥ 115 1.5 ± 0.1 ≥ 2.8
WRSFM-70/30 ≥ 70 ≤ 30 ≥ 125 1.8 ± 0.1 ≥ 3.2
WRSFM-100/46 ≥ 100 ≤ 46 ≥ 140 1.8 ± 0.1 ≥ 3.5
WRSFM-120/57 ≥ 120 ≤ 57 ≥ 155 1.8 ± 0.1 ≥ 3.5
WRSFM-140/60 ≥ 140 ≤ 60 ≥ 180 2.0 ± 0.1 ≥ 4.0
WRSFM-250/90 ≥ 250 ≤ 90 ≥ 270 2.0 ± 0.1 ≥ 4.0

 

Technical Data

Property Test Method Standard Value
Tensile strength ASTM-D 2671 ≥ 13 MPa
Elongation ASTM-D 2671 ≥ 300%
Tensile strength after aging ASTM-D 2671/120 oC, 168 hrs ≥ 11 MPa
Elongation at break after aging ASTM-D 2671/120 oC, 168 hrs ≥ 230%
Longitudinal shrinkage UL 224 ≤ 10%
Eccentricity ASTM-D 2671 < 30%
Water absorption ISO 62 ≤ 0.1%
Volume resistance IEC 93 ≥ 1x1014 Ω.cm
Dielectric Strength IEC 243 ≥ 20 kV/mm
Resistance to stress cracking ASTM-D-1693 (50 oC) No cracking
Resistance to fungus and decay ISO 846 Pass

 


  • Model: WRSFM


Your IP Address is: 3.143.110.79
ICTEA